EasyManua.ls Logo

Airtec RO Plus l - Page 71

Default Icon
135 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
71
9. Display Menu
Information and daily setup screens
Airtec HydroSens
< AHU >
Software V. 1.00
Status OK
- Software type/version and system status.
< AHU Overview >
°-1- °-2- °-3-
Step X X X
Control % XXX XXX XXX
Room %RH XXX XXX XXX
Setpoint XX XX XX
Duct %RH XXX XXX XXX
Setpoint XX XX XX
- Step, control %, room and duct %RH/setpoint.
To change setpoints, enter password.
< System >
Operation, hours XXXXXX
Pump, hours XXXXXX
Oil, hours XXXXXX
Reset Service Yes
Pressure, Bar XX.X
Inverter, Amps XX.X
Show Service popup Yes
- Hours, pressure and amps.
User password can:
- reset service (incl. oil hours).
Maintenance password can also:
- edit pump and oil hours.
- enable/disable service popup .
Shared User and Maintenance setup Screens
Valve Hours
D1.1 XXXXXX D3.1 XXXXXX
D1.2 XXXXXX D3.2 XXXXXX
D1.3 XXXXXX D3.3 XXXXXX
D2.1 XXXXXX
D2.2 XXXXXX
D2.3 XXXXXX
- Valve hours.
User password:
- read only.
Maintenance password:
- edit valve hours.
Flow Limit
D1.1 XX.X D3.1 XX.X
D1.2 XX.X D3.2 XX.X
D1.3 XX.X D3.3 XX.X
D2.1 XX.X
D2.2 XX.X
D2.3 XX.X LowFlow XX.X
- Flow limit for all valves and LowFlow.
Read only, value is automaticly stored during ow test.
Flow Test & Setup
Test Duct X.X Yes
Hysteresis, Hz XX.X
Inverter Freq, Hz XX.X
LowFlow Installed Yes
Alarm Delay, Sec. XX
Alarm On
- Flow test, hysteresis, inverter Hz, ow alarm & delay
User password can:
- run ow test (select duct/valve and change No to Yes).
- edit hysteresis.
Maintenance password can also:
- enable/disable LowFlow installed.
- set ow alarm delay.
- turn ow alarm o. After 1 hour it turns on again
Maintenance setup screens
AHU Control Setup
AHU 1 0-100%
AHU 2 Room %RH
AHU 3 O
Oset %RH ± Room/Duct
AHU 1 -X/-X
AHU 2 -X/-X
AHU 3 -X/-X
- Setup of control method and sensor oset
Control methods:
- O Deactiveated.
- 0-100% External controlsignal 0-10 V DC.
- Room %RH Room humidication sensor 0-10 V DC.
Sensor Oset ± 9 %RH.
PI Gain and time
Room
P gain xxx
I time xxx
Duct
P gain xxx
I time xxx
- Reaction setup
P gain How much it reacts (1-255).
the higher the number the more it reacts.
I time How fast it reacts (1-255).
the lower the number the faster it reacts.
Alarm %RH & Hysteresis
Low limit, %RH XX
High limit, %RH XXX
Duct 1, %RH XX
Duct 2, %RH XX
Duct 3, %RH XX
Hysteresis Downstep X
- %RH alarm limits and downstep hysteresis.
%RH alarm limits:
- Low limit Room low limit (default 10).
- High limit Room high limit (default 80).
-Duct X Duct max. limit (default 88).
Hysteresis Delayed stepdown in % control signal.
Alarm Out NC
External Alarm NC
Alarm Delay, Sec. XX
Enable 2nd PLC Yes
Valve Pause, Sec. XX
Hygiene Rinse
Rinse time, Sec. XX
Hours between XX
- Setup alarm out, 2
nd
PLC, valve pause and rinse
- Alarm Out Normaly Closed/Open.
- External Alarm IN Normaly Closed/Open.
- Ext. Alarm Delay Sec. before alarm.
- 2nd PLC Installed Y/N (AHU 3).
- Valve pause Sec. between stop and start.
Hygiene Rinse:
- Rinse time Length of hygiene rinse (sec.).
- Hours between Hours between hygiene rinse
SDcard
Backup SDcard Yes
- Setup SDcard fault message (from V.2.40)
Backup SDcard
- Yes Enables the SDcard fault screen.
- No Disables the SDcard fault screen, but
backup is still done if a SDcard is present.
Adjust By-Pass
Adjust By-Pass Yes
Pressure, Bar XX.X
- Pressure and adjusting by-pass.
Before adjusting, make sure one valve is open!
Adjust by-pass:
- change ”No” to ”Yes” (resets to ”No” after 30 sec.).
- adjust by-pass.
- return to ”No.
- lock by-pass position.
Alarm screens
Temprature pump° A
Modbus Fault° L
Inverter Fault° A
Pressure Alarm R
High Flow/No Water M
High %RH in Room 1 2 3
Low %RH in Room 1 2 3
High %RH in Duct 1 2 3
- Alarm screen.
Here you can see the active alarms - see troubleshooting.
-if the ° is shown at the rst three, the fault is still activ.
Goto alarm screen,
> 2 sec.
Reset alarms
Alarm Log
Power XXXXX
Temperature Pump XXXXX
Modbus Fault XXXXX
Inverter Fault XXXXX
High Pressure XXXXX
Max. Pressure, Bar XXX.X
Reset Press -F6-
- Alarm log screen 1.
Info about how many times an alarm has appeared.
Maintenance password:
- reset log
Alarm Log
High Flow XXXXX
High Flow/No Water XXXXX
High %RH in Room XXXXX
Low %RH in Room XXXXX
High %RH in Duct XXXXX
Reset Press -F6-
- Alarm log screen 2.
Info about how many times an alarm has appeared
Maintenance password:
- reset log
Password, service and SDcard fault screen
Password
0000
Press OK
- Setup alarm out, 2
nd
PLC, valve pause and rinse.
Goto password screen,
> 2 sec.
Enter password.
Service
- Time for service.
Appears the rst time, when the pump has run for 300 h.
It reappears for every time the pump has run for 2000 hours or
half a year, depending on what comes rst.
When leaving the screen it reappears after two days, until
”Reset Service”.
SDcard Not Present/
Fault SDcard
Fault Code: x
- SDcard not present or fault SDcard (from V.2.40).
Missing SDcard or fault in read/write on SDcard:
Fault Code 1: SDcard not present.
Fault Code 2: Datale on SDcard is full.
Fault Code 3: SDcard is broken/full/read only.
201218

Table of Contents