137
[MEMO]
<< 8 TON Heating >>
Number of operating
compressors
Apparent engine
speed (rpm (min
-1
))
Engine speed (rpm (min
-1
))
(950P)
Electromagnetic
compressor capacity
valve 1
Electromagnetic
compressor capacity
valve 2
2
3000 ERPMmax = 3000 OFF OFF
2000 2000 OFF OFF
1500 1500 OFF OFF
1000 1000 OFF OFF
800 800 OFF OFF
750 900 ON OFF
700 850 ON OFF
650 800 ON OFF
600 1000 ON OFF
550 950 ON ON
500 900 ON ON
450 850 ON ON
400 ERPMmin = 800 ON ON
1 400 1200 ON OFF
<< 15 TON Cooling >>
Number of operating
compressors
Apparent engine
speed (rpm (min
-1
))
Engine speed (rpm (min
-1
))
(3Y)
Electromagnetic
compressor capaci-
ty valve 1
Electromagnetic
compressor capaci-
ty valve 2
2
2000 ERPMmax = 2000 OFF OFF
1500 1500 OFF OFF
1000 1000 OFF OFF
600 600 OFF OFF
550 700 ON OFF
500 650 ON OFF
450 600 ON OFF
400 750 ON ON
350 700 ON ON
300 650 ON ON
250 ERPMmin = 600 ON ON
1 250 1200 ON OFF