4) Set DS2 and DS1 of the outdoor external control adapter so that they agree with the cooling / heating collective
address of the outdoor control PCB with the check mode code No. dA. (Factory set addresses are all "OFF".)
5) Set SS 2 of the outdoor external control adapter to "ON".
6) Set "Dependent collective" by setting #2 pin to "OFF" and #3 pin to "ON" in the check code No.81.
7) If you use only one cool/heat central controller, set the upper 2 bits of the outdoor external control adapter to
"OFF". If more than one cool/heat central controller is used, assign each controller with a number from 0 ~ 3
with the upper 2 bits of the address setting switch of the outdoor external control adapter.
8) Set the address with the lower 3 bits of the address setting switch of the outdoor external control adapter and
the check mode code No.dA.