Switching on and testing supply voltage
...................................................................................................................................................................................................................................
Overview
This section describes the procedure for powering the system. Please observe the order
of steps described below.
Procedure
Proceed as follows to switch on and test the power supply:
...................................................................................................................................................................................................
1
Check the voltage at the external Battery Distribution and Fuse Bay (BDFB) or at the
Power Distribution Panel (if available) and enter the measured value in the result table
(see chapter 9, “Power supply measurements” (p. 9-2)).
Result: The voltage must be in the range as given below.
DC power supply: –18 V ... 72 V
AC power supply: 90 V ... 264 V.
NOTE: Do not proceed if the voltage is outside the range.
...................................................................................................................................................................................................
2
Switch off the power.
...................................................................................................................................................................................................
3
Connect the power cable between the power interface of the 1643 AM/AMS unit and
the BDFB (or PDP).
NOTE: If an AC/DC converter is used, it has to be connected to the DC connector of
the 1643 AM/AMS unit first and then to the BDFB (or PDP).
...................................................................................................................................................................................................
4
Connect the fan power cable between the power interface of the fan unit and the
BDFB (or PDP).
...................................................................................................................................................................................................
5
Switch on the power.
...................................................................................................................................................................................................
6
Check that the green “Power” LED of the 1643 AM/AMS unit is illuminating.
Power failure
If the powering procedure described above was unsuccessful, please refer to Appendix
A, section “Power failure” (p. B-2).
Powering
...................................................................................................................................................................................................................................
365-312-802R7.2
Issue 4, June 2007
Alcatel-Lucent - Proprietary
See notice on first page
5-3
E ND OF STEPS
...................................................................................................................................................................................................