Rockwell Automation Publication 6000-UM002E-EN-P - April 2018 68
Parameters and Function Codes Chapter 4
P061Power Cell Bypass Fault Simulation-3276832767000000000000 On/OffYY
P065 Power Cell Bypass Enable Frequency
Range Lower limit
0.00 19.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 On/Off Y
P066 Power Cell Bypass Restart Enable
After Power Cell Bypassed
0 = Disable
1 = Enable
0 1111111111111 Offline Y
P068One Phase Lost Filter Time 5 100030303030303030303030303010 msOn/OffYY
P069 Current Stability Loop Enable
Frequency Range2 Upper Limit
0 100 80 80 80 80 80 80 80 80 80 80 80 80 On/Off Y
P070 Current Stability Loop Frequency
Range2 Output Scaling Factor
0 100000000000000 On/Off Y
P071 Current Stability Loop Frequency
Range3 Output Scaling Factor
0 100000000000000 On/Off Y
P072Current Stability Loop Enable Delay0 163101010101010101010101010 On/OffYYY
P073Input Voltage Loss Filter Time0 1000000000000000msOn/Off Y
P078 Power Cell Reactivation Time Upper
Limit
0 200 100 100 100 100 100 100 100 100 100 100 100 100 ms On/Off Y
P079 VFD Minimum Overload Current 0.00 399.99 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 % On/Off Y Y
P080 VFD Overload Current 0.00 399.99 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 % On/Off Y Y
P081 VFD Overload Time 0 32767 60 60 60 60 60 60 60 60 60 60 60 60 s On/Off Y Y
P082 VFD Overload Cycle Time 0 32767 600 600 600 600 600 600 600 600 600 600 600 600 s On/Off Y Y
P087 Switch Frequency Setting Enable
Code
0 = Disable
1 = Enable
0 1000000000000 Offline Y
P088 Switch Frequency Setting
0 = 600 Hz
1 = 1200 Hz
0 1000000000000 Offline Y
P089 Skip Frequency Enable
0 = Disable
1 = Enable
0 1000000000000 On/OffYY
P090Skip Frequency 1 Lower Limit0 75000000000000 On/OffYY
P091Skip Frequency 1 Upper Limit0 75000000000000 On/OffYY
P092Skip Frequency 2 Lower Limit0 75000000000000 On/OffYY
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R