71 Rockwell Automation Publication 6000-UM002E-EN-P - April 2018
Chapter 4 Parameters and Function Codes
P145 System Fault B Trip Signal Mask -32768 32767 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 Offline Y Y
P146 Line Rated Voltage 0 32767 2300 2400 3000 3300 4000 4160 6000 6300 6600 6900 10000 11000 V On/Off Y Y
P147 Line Rated Frequency 0 32767 50 50 50 50 50 50 50 50 50 50 50 50 Hz On/Off Y Y
P148Transformer Rated Power 0 32767000000000000kVAOn/OffYY
P149 Transformer Short Circuit
Impedance
0 100555555555555%On/OffYY
P151 Line Voltage Uab Scaling Factor 0.00 199.99 153.00 146.70 175.90 159.90 175.80 169.00 146.50 167.40 159.80 152.80 158.10 143.70 % On/Off Y Y
P152 Line Voltage Ubc Scaling Factor 0.00 199.99 153.00 146.70 175.90 159.90 175.80 169.00 146.50 167.40 159.80 152.80 158.10 143.70 % On/Off Y Y
P153 Line Voltage Ung Scaling Factor 0.00 199.99 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 % On/Off Y Y
P154 Line Over Voltage Fault Threshold 0.00 199.99 115.00 115.00 115.00 115.00 115.00 115.00 115.00 115.00 115.00 115.00 115.00 115.00 % On/Off Y Y
P155 Line Over Voltage Fault Delay 0 32767 10 10 10 10 10 10 10 10 10 10 10 10 ms On/Off Y Y
P156 Line Under Voltage Warning
Threshold
0 100 80 80 80 80 80 80 80 80 80 80 80 80 % On/Off Y Y
P157 Line Under Voltage Warning Delay 0 32767 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 ms On/Off Y Y
P158 Line Neutral Over Voltage Warning
Threshold
0.00 199.99 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 % On/Off Y Y
P159 Line Neutral Over Voltage Warning
Delay
0 32767 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 ms On/Off Y Y
P160 Line Neutral Over Voltage Fault
Threshold
0.00 199.99 80.00 80.00 80.00 80.00 80.00 80.00 80.00 80.00 80.00 80.00 80.00 80.00 % On/Off Y Y
P161 Line Neutral Over Voltage Fault
Delay
0 32767 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 ms On/Off Y Y
P162 Line Voltage Positive Sequence Filter
Time
0 32767 10 10 10 10 10 10 10 10 10 10 10 10 ms On/Off Y Y
P163 Line Voltage Negative Sequence
Filter Time
0 32767 10 10 10 10 10 10 10 10 10 10 10 10 ms On/Off Y Y
P164 Line Voltage Negative Sequence
Fault Threshold
0.00 199.99 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 % On/Off Y Y
P165 Line Voltage Negative Sequence
Fault Delay
0 32767 10 10 10 10 10 10 10 10 10 10 10 10 ms On/Off Y Y
P166 Line Voltage Phaser Sequence
Reverse Enable
0 = Disable
1 = Enable
0 1000000000000 On/OffYY
P168 Line Current Filter Time 0 32767 10 10 10 10 10 10 10 10 10 10 10 10 ms On/Off Y Y
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals