75 Rockwell Automation Publication 6000-UM002E-EN-P - April 2018
Chapter 4 Parameters and Function Codes
P257 Motor Stall Warning Cancellation
Threshold
0.00 199.99 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 On/Off Y
P258 DC Bus Under Voltage Fault Delay 0 32767 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 ms On/Off Y
P263 Power Loss Restart Enable
0 = Disable
1 = Enable
0 1000000000000 OfflineYY
P264Power Loss Allowable Time 0 3600606060606060606060606060s OfflineYY
P265 Power Loss Time Max Limit 0 3600 300 300 300 300 300 300 300 300 300 300 300 300 s Offline Y
P266 DC Bus Voltage Deviation Fault
Threshold
0 100 25 25 25 25 25 25 25 25 25 25 25 25 % On/Off Y Y
P267 DC Bus Voltage Deviation Fault Filter
Time
0 1000101010101010101010101010msOn/OffYY
P268 Flux Control Signal Filter Time 0.00 13663.80 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 ms On/Off Y
P269 System Derating Control Signal Filter
Time
9.60 13663.80 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 10000.08 ms On/Off Y
P270 Delayed Lockout Time of Stop
Operation
0 5000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 ms On/Off Y
P271 Flux Delay 0 5000 500 500 500 500 500 500 500 500 500 500 500 500 ms On/Off Y
P272 Flux Control Compensation Gain 0 100 25 25 25 25 25 25 25 25 25 25 25 25 % On/Off Y
P273 Flux Control Regulation Control
Enable
0 = Disable
1 = Enable
0 1111111111111 On/Off Y
P274 DC Bus Under Voltage Warning
Threshold
0 100 80 80 80 80 80 80 80 80 80 80 80 80 % On/Off Y Y
P275 DC Bus Under Voltage Warning
Hysteresis Band
0 100555555555555%On/OffYY
P276Flux Control-Lag Band Width0 100333333333313 On/Off Y
P277 DC Link Voltage Sag Scaling At Rated
Load
0 100555555555555AOn/Off Y
P278 Derating Control Enable Threshold 50.00 199.99 110.00 110.00 110.00 110.00 110.00 110.00 110.00 110.00 110.00 110.00 110.00 110.00 On/Off Y Y
P279 Derating Control Output Filter Time 9.95 1999.94 9.95 9.95 9.95 9.95 9.95 9.95 9.95 9.95 9.95 9.95 9.95 9.95 On/Off Y
P280 Low Voltage Ride Through Recovery
Voltage Boost Coefficient
0 100000000000000%On/Off Y
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R