EasyManua.ls Logo

Anderson DA2 - Page 29

Anderson DA2
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PAGE 29
NOTE: If the table contains unacceptable coordinate values, the display shows a “CONFIRM
FAILURE” message. Pressing ENTER key displays the unacceptable coordinate(s)
TDS Measurement Setup
Define the conductivity-to-TDS conversion factor:
1. With the
screen displayed, press
ØØ
ØØ
Ø
key once to display
.
2. Press ENTER key to display
.
3. Press ENTER key again to display
. Use
ØØ
ØØ
Ø and
××
××
× keys
to select a conversion factor, and press ENTER key to enter it:
NaCl: Built-in NaCl conductivity-to-TDS conversion factor.
USER DEFINED: Conductivity-to-TDS conversion factor set by user (see step 4).
4. If “USER DEFINED” was selected, you must set a conductivity-to-TDS conversion
factor:
A. With the screen displayed, press
ØØ
ØØ
Ø key once to
display .
B. Press ENTER key to display a screen like . Use arrow keys to adjust to a desired
conductivity-to-TDS conversion factor, and press ENTER key to enter it.
C. After the screen re-appears, press ESC key once to return to the screen.
CONFIG LINEAR or CONFIG T-TABLE Temperature Compensation (configuration not
needed for other compensation methods)
Only when LINEAR or TEMP TABLE is the selected temperature compensation, must the
transmitter be further configured. If the built-in NATURAL WATER properties table or NONE
was selected, disregard this subsection — no compensation configuration is needed.
LINEAR Compensation Setup
Factory defaults for LINEAR compensation are 2.00%/°C slope and 25.0°C reference
temperature. These values are appropriate for most aqueous solutions. Use chemical
handbook tables to find values for uncommon solutions. To enter different values:
1. With the
or screen displayed,
press
ØØ
ØØ
Ø key until screen appears.
2. Press ENTER key to display
.

Table of Contents

Related product manuals