Avertissements Installation
7878
Warnings Installation
• Legislation on the handling of refrigerant uids:
Decree 2007/737 and its implementing orders.
• This air conditioner must only be commissioned by a
qualied installer holding a certicate of professional
competence in accordance with articles R 543-75 to
123 of the environmental code and its implementing
orders. This also applies to any work carried out on
equipment involving the handling of refrigerant uid.
• NF C 15-100 and its amending provisions: low vol-
tage electrical installations - Rules.
R32 REFRIGERANT FLUID:
• To install the unit, use R32 refrigerant uid to top up the
charge, as well as tools and connections which are compa-
tible with R32.
• This ammable uid requires minimum dimensions for the
room in which the unit is installed, stored or used. Make sure
that the site application is compatible with the size of the
components being used and the installation's uid charge
(compliance with standard EN 378-1 and IEC 60335-2-40).
• Do not introduce any substance other than the recom-
mended refrigerant uid into the unit.
• Do not release refrigerant uid into the atmosphere. Ven-
tilate the room in the event of a refrigerant leak during ins-
tallation. Once installation is complete, there should be no
refrigerant leaks in the circuit. An R32 uid leak combined
with a ammable source can result in the release of toxic
gas.
• Do not touch the refrigerant uid if there are leaks from the
connections, etc. Direct contact can cause frostbite.