PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 101
30E –
Flow Sensor Type
Options:
None (default) Pulses per minute
Switch Pulses per unit
Analog
Selects which type of sensor is associated with the flow sensor
input on the smart card.
30F –
Flow Units
Options:
litres/second (default)
litres/minute
gallons/second
gallons/minute
Selects which units the sensor will use to report the measured
flow.
30G –
Flow at 4 mA
Range:
0 – 5000
0
Calibrates the soft starter to the 4 mA (0%) level of the flow
sensor input.
30H –
Flow at 20 mA
Range:
0 – 5000
0
Calibrates the soft starter to the 20 mA (100%) level of the flow
sensor input.
30I –
Units per Minute at Max Flow
Range:
0 – 5000
0
Calibrates the soft starter to the maximum flow volume of the
flow sensor.
30J –
Pulses per Minute at Max Flow
Range:
0 – 20000
0
Calibrates the soft starter to the maximum flow volume of the
flow sensor.
30K –
Units per Pulse
Range:
0 – 1000
0
Set to match how many units the flow sensor will measure for
each pulse.