EasyManua.ls Logo

AuCom EMX4i - Page 102

AuCom EMX4i
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 101
30E
Flow Sensor Type
Options:
None (default) Pulses per minute
Switch Pulses per unit
Analog
Description:
Selects which type of sensor is associated with the flow sensor
input on the smart card.
30F
Flow Units
Options:
litres/second (default)
litres/minute
gallons/second
gallons/minute
Description:
Selects which units the sensor will use to report the measured
flow.
30G
Flow at 4 mA
Range:
0 5000
Default:
0
Description:
Calibrates the soft starter to the 4 mA (0%) level of the flow
sensor input.
30H
Flow at 20 mA
Range:
0 5000
Default:
0
Description:
Calibrates the soft starter to the 20 mA (100%) level of the flow
sensor input.
30I
Units per Minute at Max Flow
Range:
0 5000
Default:
0
Description:
Calibrates the soft starter to the maximum flow volume of the
flow sensor.
30J
Pulses per Minute at Max Flow
Range:
0 20000
Default:
0
Description:
Calibrates the soft starter to the maximum flow volume of the
flow sensor.
30K
Units per Pulse
Range:
0 1000
Default:
0
Description:
Set to match how many units the flow sensor will measure for
each pulse.

Table of Contents

Related product manuals