PROGRAMMABLE PARAMETERS
76 EMX4i User Manual 710-14888-00C
3L
Stop Time-2
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets the time for soft stopping the motor using timed voltage
ramp or Adaptive Control.
If a main contactor is installed, the contactor must remain
closed until the end of the stop time. Use the main contactor
output (33, 34) to control the main contactor.
3M
Adaptive Stop Profile-2
Options:
Early Deceleration
Constant Deceleration (default)
Late Deceleration
Description:
Selects which profile the EMX4i will use for an Adaptive Control
soft stop.
3N
Adaptive Control Gain-2
Range:
1%~200%
Default:
75%
Description:
Adjusts the performance of Adaptive Control. This setting
affects both starting and stopping control.
3O
Multi Pump-2
Options:
Single Pump (default)
Manifold Pump
Description:
Adjusts the performance of adaptive control to suit installations
with multiple pumps connected to a common outlet manifold.
3P
Start Delay-2
Range:
0:00 - 60:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay after the starter receives a start command, before it
starts the motor.
3Q
DC Brake Torque-2
Range:
20% - 100%
Default:
20%
Description:
Sets the amount of brake torque the EMX4i will use to slow the
motor.
3R
DC Brake Time-2
Range:
0:01 - 0:30 (minutes:seconds)
Default:
1 second
Description:
Sets the duration for DC injection during a braking stop.