PROGRAMMABLE PARAMETERS
76 EMX4i User Manual 710-14888-00C
0:00 - 4:00 (minutes:seconds)
0 second
Sets the time for soft stopping the motor using timed voltage
ramp or Adaptive Control.
If a main contactor is installed, the contactor must remain
closed until the end of the stop time. Use the main contactor
output (33, 34) to control the main contactor.
3M –
Adaptive Stop Profile-2
Options:
Early Deceleration
Constant Deceleration (default)
Late Deceleration
Selects which profile the EMX4i will use for an Adaptive Control
soft stop.
3N –
Adaptive Control Gain-2
Range:
1%~200%
75%
Adjusts the performance of Adaptive Control. This setting
affects both starting and stopping control.
3O –
Multi Pump-2
Options:
Single Pump (default)
Manifold Pump
Adjusts the performance of adaptive control to suit installations
with multiple pumps connected to a common outlet manifold.
3P –
Start Delay-2
Range:
0:00 - 60:00 (minutes:seconds)
0 second
Sets a delay after the starter receives a start command, before it
starts the motor.
3Q –
DC Brake Torque-2
Range:
20% - 100%
20%
Sets the amount of brake torque the EMX4i will use to slow the
motor.
3R –
DC Brake Time-2
Range:
0:01 - 0:30 (minutes:seconds)
1 second
Sets the duration for DC injection during a braking stop.