PROGRAMMABLE PARAMETERS
102 EMX4i User Manual 710-14888-00C
30L –
Depth Sensor Type
Options:
None (default)
Switch
Analog
Selects which type of sensor is associated with the depth sensor
input on the smart card.
30M –
Depth Units
Options:
metres (default)
feet
Selects which units the sensor will use to report the measured
depth.
30N –
Depth at 4 mA
Range:
0 – 1000
0
Calibrates the soft starter to the 4 mA (0%) level of the depth
sensor input.
30O –
Depth at 20 mA
Range:
0 – 1000
0
Calibrates the soft starter to the 20 mA (100%) level of the depth
sensor input.
9.19 31 Flow Protection
The parameters in this group are only active if a smart card is installed.
Flow protection uses terminals B33, B34 or C23, C24 on the smart card.
31A –
High Flow Trip Level
Range:
0 – 5000
10
Sets the trip point for high flow protection.
31B –
Low Flow Trip Level
Range:
1 – 5000
5
Sets the trip point for low flow protection.
31C –
Flow Start Delay
Range:
00:00:50 - 30:00:00 mm:ss:ms
00:00:500 ms
Sets a delay before a flow protection trip can occur. The delay is
counted from the time a start signal is received. The flow level is
ignored until the start delay has elapsed.