INSTALLATION
710-14888-00C EMX4i User Manual 33
4.8 Quick Setup
The Quick Setup Menu makes it easy to configure the EMX4i for common
applications. The EMX4i guides you through the most common installation
parameters, and suggests a typical setting for the application. You can adjust each
parameter to suit your exact requirements.
All other parameters remain at default values. To change other parameter values
or review the default settings, use the menu (refer to
Parameter List
for details).
Always set parameter 1B
Motor Full Load Current
to match the motor's nameplate
full load current.
Application
Start Mode
Start Ramp Time
(seconds)
Initial Current
(%)
Current Limit
(%)
Adaptive Start
Profile
Stop Mode
Stop Time
(seconds)
Adaptive Stop
Profile
Pump Centrifugal
Adaptive
Control
10
200
500
Early
accel.
Adaptive
Control
15
Late
decel.
Pump bore Adaptive
Control
3 200 500 Early
accel.
Adaptive
Control
3 Late
decel.
Pump Hydraulic
Constant
Current
2
200
350
n/a
Coast To
Stop
n/a
n/a
Fan Damped Constant
Current
2 200 350 n/a Coast To
Stop
n/a n/a
Fan Undamped
Constant
Current
2
200
450
n/a
Coast To
Stop
n/a
n/a
Compressor
Screw
Constant
Current
2 200 400 n/a Coast To
Stop
n/a n/a
Compressor
Recip
Constant
Current
2
200
450
n/a
Coast To
Stop
n/a
n/a
Conveyor Constant
Current
5 200 450 n/a Coast To
Stop
n/a n/a
Bow thruster
Constant
Current
5
100
400
n/a
Coast To
Stop
n/a
n/a
Bandsaw Constant
Current
2 200 450 n/a Coast To
Stop
n/a n/a
NOTE
The Adaptive Start and Stop Profile settings only apply when using Adaptive
Control. The settings are ignored for all other start and stop modes.