INSTALLATION
710-14888-00C EMX4i User Manual 33
4.8 Quick Setup
The Quick Setup Menu makes it easy to configure the EMX4i for common
applications. The EMX4i guides you through the most common installation
parameters, and suggests a typical setting for the application. You can adjust each
parameter to suit your exact requirements.
All other parameters remain at default values. To change other parameter values
or review the default settings, use the menu (refer to
Parameter List
for details).
Always set parameter 1B
Motor Full Load Current
to match the motor's nameplate
full load current.
Start Ramp Time
(seconds)
Control
accel.
Control
decel.
Pump bore Adaptive
Control
3 200 500 Early
accel.
Adaptive
Control
3 Late
decel.
Current
Stop
Fan Damped Constant
Current
2 200 350 n/a Coast To
Stop
n/a n/a
Current
Stop
Compressor
Screw
Constant
Current
2 200 400 n/a Coast To
Stop
n/a n/a
Recip
Current
Stop
Conveyor Constant
Current
5 200 450 n/a Coast To
Stop
n/a n/a
Current
Stop
Bandsaw Constant
Current
2 200 450 n/a Coast To
Stop
n/a n/a
The Adaptive Start and Stop Profile settings only apply when using Adaptive
Control. The settings are ignored for all other start and stop modes.