EasyManua.ls Logo

AuCom EMX4i - 8.7 Typical Control Methods

AuCom EMX4i
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPERATION
710-14888-00C EMX4i User Manual 49
8.7 Typical Control Methods
The requirements of an application differ between each installation, but the
methods listed below are often a good starting point for common applications.
Application
Start Mode
Start Ramp
Time
(seconds)
Initial Current
(%FLC)
Current Limit
(%FLC)
Stop Mode
Stop Time
(seconds)
Bow thruster
Constant Current
5
100
400
Coast To Stop
n/a
Centrifuge (Separator)
Constant Current
1
200
450
Coast To Stop
n/a
Chipper
Constant Current
1
200
450
Coast To Stop
n/a
Compressor - reciprocating
- loaded
Constant Current
1 200 450 Coast To Stop n/a
Compressor - reciprocating
- unloaded
Constant Current
1 200 400 Coast To Stop n/a
Compressor - screw -
loaded
Constant Current
1 200 400 Coast To Stop n/a
Compressor - screw -
unloaded
Constant Current
1 200 350 Coast To Stop n/a
Conveyor - horizontal Constant Current
5 200 400 TVR Soft Stop 10
Conveyor - inclined
Constant Current
2
200
450
Coast To Stop
n/a
Conveyor - vertical (bucket)
Constant Current
2
200
450
Coast To Stop
n/a
Crusher - cone
Constant Current
1
200
350
Coast To Stop
n/a
Crusher - jaw Constant Current
1 200 450 Coast To Stop n/a
Crusher - rotary Constant Current
1 200 400 Coast To Stop n/a
Debarker Constant Current
1 200 350 Coast To Stop n/a
Fan - axial (damped) Constant Current
1 200 350 Coast To Stop n/a
Fan - axial (undamped) Constant Current
1 200 450 Coast To Stop n/a
Fan - centrifugal (damped) Constant Current
1 200 350 Coast To Stop n/a
Fan - centrifugal
(undamped)
Constant Current
1 200 450 Coast To Stop n/a
Fan - high pressure Constant Current
1 200 450 Coast To Stop n/a
Mill - ball Constant Current
1 200 450 Coast To Stop n/a
Mill - hammer Constant Current
1 200 450 Coast To Stop n/a
Pump - bore
Adaptive Control
(Early accel.)
3 n/a 500
Adaptive Control
(Late decel.)
3
Pump - centrifugal
Adaptive Control
(Early accel.)
10 n/a 500
Adaptive Control
(Late decel.)
15
Pump - Hydraulic Constant Current
2 200 350 Coast To Stop n/a
Pump - positive
displacement
Adaptive Control
(Const. accel.)
10 n/a 400
Adaptive Control
(Const. decel.)
10

Table of Contents