PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 77
3S –
Brake Current Limit-2
Range:
100% - 600% FLC
250%
Sets the current limit for soft brake.
3T –
Soft Brake Delay-2
Range:
400 - 2000 milliseconds
400 milliseconds
Sets the time the soft starter will wait after a stop signal is
received, before it begins to supply braking current to the motor.
Set to allow time for K1 and K2 to switch.
9.8 4 Auto-Start/Stop
The EMX4i can be configured to automatically start and/or stop the motor at a
particular time, or run it in cycles of a specified duration.
4A –
Auto-Start/Stop Mode
Options:
Disable (default) Enable Timer Mode
Enable Clock Mode
Enable or disable auto-start/stop operation.
00:00 - 23:59 hh:mm
00:00
Sets the duration for the starter to run, after a timer mode
auto-start.
00:00 - 23:59 hh:mm
00:00
Sets the duration for the starter to remain stopped, when
operating in timer mode.
Disable (default)
Disables auto-start/stop control. Any times
scheduled in parameters 4E or 4F will be
ignored.
Start Only
Enable
Enables auto-start control. Any auto-stop
times scheduled in parameter 4F will be
ignored.
Enable
Enables auto-stop control. Any auto-start
times scheduled in parameter 4E will be
ignored.
Start/Stop
Enable
Enables auto-start and auto-stop control.
Enables or disables auto-start/stop for Sunday.