PROGRAMMABLE PARAMETERS
86 EMX4i User Manual 710-14888-00C
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Trip Starter Log Only
Selects the soft starter's response to the protection event.
9.11 7 Inputs
Override:
Network
Overrides the setting of 1A and sets the
command source to the communications
network.
Command
Override: Digital
Overrides the setting of 1A and sets the
command source to the digital inputs.
Command
Override:
Keypad
Overrides the setting of 1A and sets the
command source to the remote keypad.
(default)
A closed circuit across 13, 14 trips the soft
starter.
Input Trip (N/C)
An open circuit across 13, 14 trips the soft
starter.
Emergency
Mode
A closed circuit across 13, 14 activates
emergency mode. When the EMX4i receives a
start command, it will continue to run until a
stop command is received, ignoring all trips
and warnings.
Jog Forward Activates jog operation in a forward direction.
Activates jog operation in reverse direction.
Sensor
An open circuit across 13, 14 indicates to the
soft starter that the motor has reached a
standstill. The soft starter requires a normally
open zero speed sensor.
Motor Set Select
A closed circuit across 13, 14 instructs the
starter to use the secondary motor
configuration for the next start/stop cycle.
Direction
A closed circuit across 13, 14 instructs the
starter to reverse the phase sequence for the
next start.
Activates the pump clean function.
Selects the function of Input A.