PROGRAMMABLE PARAMETERS
80 EMX4i User Manual 710-14888-00C
9.9 5 Protection Levels
5A –
Current Imbalance
Range:
10% - 50%
30%
Sets the trip point for current imbalance protection.
5B –
Current Imbalance Delay
Range:
0:00 - 4:00 (minutes:seconds)
3 seconds
Slows the EMX4i's response to current imbalance, avoiding trips
due to momentary fluctuations.
0% - 100%
20%
Sets the trip point for undercurrent protection, as a percentage
of motor full load current. Set to a level between the motor's
normal working range and the motor's magnetising (no load)
current (typically 25% to 35% of full load current). A setting of
0% disables undercurrent protection.
5D –
Undercurrent Delay
Range:
0:00 - 4:00 (minutes:seconds)
5 seconds
Slows the EMX4i's response to undercurrent, avoiding trips due
to momentary fluctuations.
80% - 600%
400%
Sets the trip point for overcurrent protection, as a percentage of
motor full load current.
5F –
Overcurrent Delay
Range:
0:00 - 1:00 (minutes:seconds)
0 second
Slows the EMX4i's response to overcurrent, avoiding trips due to
momentary overcurrent events.
100 - 1000 V
350
Sets the trip point for undervoltage protection. Set as required.
Voltage protections will not operate correctly until the starter is in Run mode.