PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 95
10K
User Parameter 4
Options:
Refer to parameter 10H
User Parameter 1
for details.
Default:
Motor pf
Description:
Selects which information will be displayed on the
programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
10L
User Parameter 5
Options:
Refer to parameter 10H
User Parameter 1
for details.
Default:
Motor Power
Description:
Selects which information will be displayed on the
programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
10M
User Parameter 6
Options:
Refer to parameter 10H
User Parameter 1
for details.
Default:
Motor Temp (%)
Description:
Selects which information will be displayed on the
programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
9.15 11 Pump Clean
11A
Reverse Torque
Range:
20% - 100%
Default:
20%
Description:
Sets the torque level for reverse jog operation during pump
clean.
11B
Reverse Time
Range:
0:00 - 1:00 (minutes:seconds)
Default:
10 seconds
Description:
Sets the time for the starter to operate in reverse jog during a
pump clean cycle.
11C
Forward Current Limit
Range:
100% - 600% FLC
Default:
100%
Description:
Sets the current limit for forward start operation during pump
clean.
11D
Forward Time
Range:
0:00 - 1:00 (minutes:seconds)
Default:
10 seconds
Description:
Sets the time for the starter to run the motor after a forward
start, during a pump clean cycle.