PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 95
10K –
User Parameter 4
Options:
Refer to parameter 10H
User Parameter 1
for details.
Motor pf
Selects which information will be displayed on the
programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
10L –
User Parameter 5
Options:
Refer to parameter 10H
User Parameter 1
for details.
Motor Power
Selects which information will be displayed on the
programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
10M –
User Parameter 6
Options:
Refer to parameter 10H
User Parameter 1
for details.
Motor Temp (%)
Selects which information will be displayed on the
programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
9.15 11 Pump Clean
11A –
Reverse Torque
Range:
20% - 100%
20%
Sets the torque level for reverse jog operation during pump
clean.
11B –
Reverse Time
Range:
0:00 - 1:00 (minutes:seconds)
10 seconds
Sets the time for the starter to operate in reverse jog during a
pump clean cycle.
11C –
Forward Current Limit
Range:
100% - 600% FLC
100%
Sets the current limit for forward start operation during pump
clean.
11D –
Forward Time
Range:
0:00 - 1:00 (minutes:seconds)
10 seconds
Sets the time for the starter to run the motor after a forward
start, during a pump clean cycle.