SYSTEM DESIGN
14 EMX4i User Manual 710-14888-00C
3.6 Physical Installation
DD
17044.B
C
C
B
A
Between starters
Solid surfaces
A
B
C
D
> 100 mm (3.9 inch) > 10 mm (0.4 inch) > 100 mm (3.9 inch) > 10 mm (0.4 inch)
3.7 Accessories
Expansion Cards
The EMX4i offers expansion cards for users requiring additional inputs and outputs
or advanced functionality. Each EMX4i can support a maximum of one expansion
card.
Smart Card
The smart card has been designed to support integration with pumping applications
and provides the following additional inputs and outputs:
3 x digital inputs
3 x 4-20 mA transducer inputs
1 x RTD input
1 x USB-B port
Remote keypad connector
Communication Expansion Cards
The EMX4i supports network communication via easy-to-install communications
expansion cards. Each communications card includes a remote keypad connector
port.
Available protocols:
DeviceNet, Ethernet/IP, Modbus RTU, Modbus TCP, Profibus, Profinet.