EasyManua.ls Logo

AuCom EMX4i - 9.17 20 Advanced

AuCom EMX4i
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 99
12T –
DHCP
Options:
Disable (default)
Enable
Description:
Selects whether the communications card will accept an IP
address assigned by DHCP.
NOTE
DHCP addressing is available with Modbus TCP and Ethernet/IP. DHCP
addressing is not supported with Profinet.
12U –
Location ID
Range:
0 - 65535
Default:
0
Description:
Sets the soft starter's unique location ID.
9.17 20 Advanced
20A –
Tracking Gain
Range:
1% - 200%
Default:
50%
Description:
Fine-tunes the behaviour of the adaptive control algorithm.
20B –
Pedestal Detect
Range:
0% - 200%
Default:
80%
Description:
Adjusts the behaviour of the adaptive control algorithm for soft
stop.
20C –
Bypass Contactor Delay
Range:
100 – 2000 milliseconds
Default:
150 milliseconds
Description:
Sets the starter to match the bypass contactor closing/opening
time. Set according to the specifications of the bypass contactor
used. If this time is too short, the starter will trip.
20D –
Model Rating
Range:
0020~0580
Default:
Model dependent
Description:
The soft starter’s internal model reference, as shown on the
silver label on the side of the unit (
).
M/R: 0085 Made in New Zealand
RoHS
18595.B
1
NOTE
This parameter can only be adjusted by authorised servicing agents.

Table of Contents