PROGRAMMABLE PARAMETERS
96 EMX4i User Manual 710-14888-00C
11E –
Pump Stop Mode
Options:
Coast To Stop (default)
TVR Soft Stop
Selects the stop mode for pump clean.
11F –
Pump Stop Time
Range:
0:00 - 1:00 (minutes:seconds)
10 seconds
Sets the stopping time for the starter during a pump clean cycle.
11G –
Pump Clean Cycles
Range:
1 – 5
1
Sets how many times the soft starter will repeat the pump clean
cycle.
9.16 12 Communications Card
12A –
Modbus Address
Range:
1 - 254
1
Sets the Modbus RTU network address for the soft starter.
12B –
Modbus Baud Rate
Options:
4800
9600 (default)
19200
38400
Selects the baud rate for Modbus RTU communications.
12C –
Modbus Parity
Options:
None (default)
Odd
Even
10-bit
Selects the parity for Modbus RTU communications.
12D –
Modbus Timeout
Options:
Off (default)
10 seconds
60 seconds
100 seconds
Selects the timeout for Modbus RTU communications.