PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 97
12E –
Devicenet Address
Range:
0 - 63
0
Sets the DeviceNet network address for the soft starter.
12F –
Devicenet Baud Rate
Options:
125 kB (default)
250 kB
500 kB
Selects the baud rate for DeviceNet communications.
12G –
Profibus Address
Range:
1 - 125
1
Sets the Profibus network address for the soft starter.
12H –
Gateway Address
Range:
0 - 255
192
Sets the first component of the network gateway address. The
gateway address is set using parameters 12H~12K and the
default address is 192.168.0.100.
12I –
Gateway Address
2
Range:
0 - 255
168
Sets the second component of the network gateway address.
12J –
Gateway Address
3
Range:
0 - 255
0
Sets the third component of the network gateway address.
12K –
Gateway Address
4
Range:
0 - 255
100
Sets the fourth component of the network gateway address.
The network address can also be set via the Network Address options in the
Setup Tools. Refer to
Network Address
on page 38 for details.
0 - 255
192
Sets the first component of the soft starter's IP address, for
Ethernet communications. The IP address is set using
parameters 12L~12O and the default address is 192.168.0.2.