PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 97
12E
Devicenet Address
Range:
0 - 63
Default:
0
Description:
Sets the DeviceNet network address for the soft starter.
12F
Devicenet Baud Rate
Options:
125 kB (default)
250 kB
500 kB
Description:
Selects the baud rate for DeviceNet communications.
12G
Profibus Address
Range:
1 - 125
Default:
1
Description:
Sets the Profibus network address for the soft starter.
12H
Gateway Address
Range:
0 - 255
Default:
192
Description:
Sets the first component of the network gateway address. The
gateway address is set using parameters 12H~12K and the
default address is 192.168.0.100.
12I
Gateway Address
2
Range:
0 - 255
Default:
168
Description:
Sets the second component of the network gateway address.
12J
Gateway Address
3
Range:
0 - 255
Default:
0
Description:
Sets the third component of the network gateway address.
12K
Gateway Address
4
Range:
0 - 255
Default:
100
Description:
Sets the fourth component of the network gateway address.
NOTE
The network address can also be set via the Network Address options in the
Setup Tools. Refer to
Network Address
on page 38 for details.
12L
IP Address
Range:
0 - 255
Default:
192
Description:
Sets the first component of the soft starter's IP address, for
Ethernet communications. The IP address is set using
parameters 12L~12O and the default address is 192.168.0.2.