PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 85
Selects the soft starter's response to the protection event. If set
to Stop, the EMX4i will perform a soft stop, then can be restarted
without a reset.
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Trip Starter Log Only
Selects the soft starter's response to the protection event.
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Trip Starter Log Only
Selects the soft starter's response to the protection event.
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Selects the soft starter's response to the protection event.
6Q –
Motor Overtemperature
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Trip Starter Log Only
Selects the soft starter's response to the protection event.
6R –
Motor Thermistor Circuit
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Trip Starter Log Only
Selects the soft starter's response to the protection event.
6S –
Shorted SCR Action
Options:
3-Phase Control Only (default)
PowerThrough
Selects whether the soft starter will allow PowerThrough
operation, if the soft starter is damaged on one phase. The soft
starter will use two-phase control, allowing the motor to
continue operating in critical applications. Refer to
PowerThrough
on page 47 for further information.