PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 87
7B
Input A Trip
Options:
Always Active
A trip can occur at any time when the soft
starter is receiving power.
Operating Only
(default)
A trip can occur while the soft starter is
running, stopping or starting.
Run Only
A trip can only occur while the soft starter is
running.
Description:
Selects when an input trip can occur.
7C
Input A Trip Delay
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay between the input activating and the soft starter
tripping.
7D
Input A Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay before an input trip can occur. The initial delay is
counted from the time a start signal is received. The state of the
input is ignored until the initial delay has elapsed.
7E
Input B Function
Options:
Input Trip (N/O) (default) Zero Speed Sensor
Input Trip (N/C) Motor Set Select
Emergency Mode Reverse Direction
Jog Forward Pump Clean
Jog Reverse
Description:
Selects the function of Input B. Refer to parameter 7A
Input A
Function
for details.
7F
Input B Trip
Options:
Always Active
Operating Only (default)
Run Only
Description:
Selects when an input trip can occur.
7G
Input B Trip Delay
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay between the input activating and the soft starter
tripping.