PROGRAMMABLE PARAMETERS
88 EMX4i User Manual 710-14888-00C
7H –
Input B Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
0 second
Sets a delay before an input trip can occur. The initial delay is
counted from the time a start signal is received. The state of the
input is ignored until the initial delay has elapsed.
7I –
Reset/Enable Logic
Options:
Normally Closed (default)
Normally Open
Selects whether the reset input (10, 11) is normally open or
normally closed.
If the reset input is active, the starter will not operate.
Input A Trip (default) Controller
Low Pressure PLC
High Pressure Vibration Alarm
Pump Fault Field Trip
Starter Disable Feeder Protection
Custom Message
Selects a message for the keypad to display when Input A is active.
The custom message can be loaded via the USB port. Refer to
USB Save & Load
on page 36 for details.
Pump Fault Field Trip
Low Level Interlock Trip
High Level Motor Temperature
No Flow Motor Protection
Starter Disable Feeder Protection
Custom Message
Selects a message for the keypad to display when Input B is active.