PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 107
36F
High Flow
Options:
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Trip Starter Log Only
Description:
Selects the soft starter's response if the flow exceeds the high
flow trip level (parameter 31A).
36G
Low Flow
Options:
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Trip Starter Log Only
Description:
Selects the soft starter's response if the flow falls below the low
flow trip level (parameter 31B).
36H
Flow Switch
Options:
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response if the flow sensor closes
(switch type sensors only).
36I
Well Depth
Options:
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Trip Starter Log Only
Description:
Selects the soft starter's response if the depth falls below the
depth trip level (parameter 34A) or the depth switch sensor
closes.
36J
RTD/PT100 B
Options:
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Trip Starter Log Only
Description:
Selects the soft starter's response to the protection event.