TROUBLESHOOTING
710-14888-00C EMX4i User Manual 113
Display
Possible cause/Suggested solution
Current imbalance
Current imbalance can be caused by problems with the motor,
the environment or the installation, such as:
An imbalance in the incoming mains voltage
A problem with the motor windings
A light load on the motor
A phase loss on input terminals L1, L2 or L3 during Run mode
An SCR that has failed open circuit. A failed SCR can only be
definitely diagnosed by replacing the SCR and checking the
starter's performance.
Related parameters: 5A, 5B, 6C
Current Read Err Lx
Where 'X' is 1, 2 or 3.
Internal fault (PCB fault). The output from the CT circuit is not
close enough to zero when the SCRs are turned off. Contact your
local supplier for advice.
Related parameters: None
Depth Sensor
The smart card has detected a fault with the depth sensor.
Related parameters: 30L, 36C
EEPROM fail
An error occurred loading data from the EEPROM to RAM when
the keypad powered up. If the problem persists, contact your
local distributor.
Related parameters: None
Excess start time
Excess start time trip can occur in the following conditions:
parameter 1B
Motor Full Load Current
is not appropriate for
the motor
parameter 2D
Current Limit
has been set too low
parameter 2B
Start Ramp Time
has been set greater than the
setting for 5O
Excess Start Time
parameter 2B
Start Ramp Time
is set too short for a high
inertia load when using Adaptive Control
Related parameters: 1B, 2B, 2D, 3D, 3F
Firing Fail Px
Where 'X' is phase 1, 2 or 3.
The SCR did not fire as expected. The SCR may be faulty or there
may be an internal wiring fault.
Related parameters: None