PROGRAMMABLE PARAMETERS
64 EMX4i User Manual 710-14888-00C
Parameter Group
Default Setting
4R
Thursday Stop Time
00:00 (hh:mm)
4S
Friday Mode
Start/Stop Disable
4T
Friday Start Time
00:00 (hh:mm)
4U
Friday Stop Time
00:00 (hh:mm)
4V
Saturday Mode
Start/Stop Disable
4W
Saturday Start Time
00:00 (hh:mm)
4X
Saturday Stop Time
00:00 (hh:mm)
5
Protection Levels
5A
Current Imbalance
30%
5B
Current Imbalance Delay
00:03 (mm:ss)
5C
Undercurrent
20%
5D
Undercurrent Delay
00:05 (mm:ss)
5E
Overcurrent
400%
5F
Overcurrent Delay
00:00 (mm:ss)
5G
Undervoltage
350 V
5H
Undervoltage Delay
00:01 (mm:ss)
5I
Overvoltage
500 V
5J
Overvoltage Delay
00:01 (mm:ss)
5K
Underpower
10%
5L
Underpower Delay
00:01 (mm:ss)
5M
Overpower
150%
5N
Overpower Delay
00:01 (mm:ss)
5O
Excess Start Time
00:20 (mm:ss)
5P
Restart Delay
00:10 (mm:ss)
5Q
Starts per Hour
0
5R
Phase Sequence
Any Sequence
6
Protection Actions
6A
Auto-Reset Count
0
6B
Auto-Reset Delay
00:05 (mm:ss)
6C
Current Imbalance
Soft Trip and Log
6D
Undercurrent
Soft Trip and Log
6E
Overcurrent
Soft Trip and Log
6F
Undervoltage
Soft Trip and Log
6G
Overvoltage
Soft Trip and Log

Table of Contents