PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 73
Coast To Stop
TVR Soft Stop (default)
Adaptive Control
DC Brake
Soft Brake
Selects the stop mode.
0:00 - 4:00 (minutes:seconds)
0 second
Sets the time for soft stopping the motor using timed voltage
ramp or Adaptive Control.
If a main contactor is installed, the contactor must remain
closed until the end of the stop time. Use the main contactor
output (33, 34) to control the main contactor.
2K –
Adaptive Stop Profile
Options:
Early Deceleration
Constant Deceleration (default)
Late Deceleration
Selects which profile the EMX4i will use for an Adaptive Control
soft stop.
2L –
Adaptive Control Gain
Range:
1% - 200%
75%
Adjusts the performance of Adaptive Control. This setting
affects both starting and stopping control.
Single Pump (default)
Manifold Pump
Adjusts the performance of adaptive control to suit installations
with multiple pumps connected to a common outlet manifold.
0:00 - 60:00 (minutes:seconds)
0 second
Sets a delay after the starter receives a start command, before it
starts the motor.