PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual 83
6C
Current Imbalance
Options:
Soft Trip and
Log (default)
The soft starter will stop the motor as
selected in parameter 2I or 3K
Stop Mode
,
then enter trip state. The trip must be reset
before the EMX4i can restart.
Soft Trip and
Reset
The soft starter will stop the motor as
selected in parameter 2I or 3K
Stop Mode
,
then enter trip state. The trip will reset after
the auto-reset delay
Trip Starter
The soft starter will remove power and the
motor will coast to stop. The trip must be
reset before the EMX4i can restart.
Trip and Reset
The soft starter will remove power and the
motor will coast to stop. The trip will reset
after the auto-reset delay
Warn and Log
The protection will be written to the event log
and the display will show a warning message,
but the soft starter will continue to operate.
Log Only
The protection will be written to the event log
but the soft starter will continue to operate.
Description:
Selects the soft starter's response to each protection. All
protection events are written to the event log.
6D
Undercurrent
Options:
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Trip Starter Log Only
Description:
Selects the soft starter's response to the protection event.
6E
Overcurrent
Options:
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description:
Selects the soft starter's response to the protection event.
6F
Undervoltage
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter Log Only
Description:
Selects the soft starter's response to the protection event.