PROGRAMMABLE PARAMETERS
90 EMX4i User Manual 710-14888-00C
8C –
Relay A Off Delay
Range:
0:00 - 5:00 (minutes:seconds)
0 second
Sets the delay for changing the state of Relay A.
8D –
Relay B Function
Options:
Off Low Current Flag
Ready High Current Flag
Run (default) Motor Temperature Flag
Warning Soft Brake Relay
Trip Reversing Contactor
Selects the function of Relay B (normally open). Refer to
parameter 8A
Relay A Function
for details.
8E –
Relay B On Delay
Range:
0:00 - 5:00 (minutes:seconds)
0 second
Sets the delay for closing Relay B.
8F –
Relay B Off Delay
Range:
0:00 - 5:00 (minutes:seconds)
0 second
Sets the delay for re-opening Relay B.
The EMX4i has low and high current flags to give early warning of abnormal
operation. The current flags can be configured to indicate an abnormal current level
during operation, between the normal operating level and the undercurrent or
instantaneous overcurrent trip levels. The flags can signal the situation to external
equipment via one of the programmable outputs.
The flags clear when the current returns within the normal operating range by 10%
of the programmed flag value.
1% - 100% FLC
50%
Sets the level at which the low current flag operates, as a
percentage of motor full load current.
8H –
High Current Flag
Range:
50% - 600% FLC
100%
Sets the level at which the high current flag operates, as a
percentage of motor full load current.