Features and functions
Terminal plan according to order number enclosed with deliveryTerminal plan
B1 according to EN ISO 5210Standard:Valve attachment
A, B2, B3, B4, C, D according to EN ISO 5210
A, B, D, E according to DIN 3210
C according to DIN 3338
Option:
Special valve attachments: AF, AK, AG, B3D, ED, DD, IB1, IB3
A prepared for permanent lubrication of stem
Electromechanical control unit
Counter gear mechanism for end positions OPEN and CLOSED
Turns per stroke: 2 to 500 (standard) or 2 to 5,000 (option)
Limit switching
Single switch (1 NC and 1 NO) for each end position, not galvanically isolatedStandard:
Tandem switch (2 NC and 2 NO) for each end position, switches galvanically isolated
Triple switch (3 NC and 3 NO) for each end position, switches galvanically isolated
Intermediate position switches (DUO limit switching), adjustable for each direction of op-
eration
Options:
Torque switching adjustable for directions OPEN and CLOSETorque switching
Single switch (1 NC and 1 NO) for each direction, not galvanically isolatedStandard:
Tandem switch (2 NC and 2 NO) for each direction, switches galvanically isolatedOption:
Silver (Ag)Standard:Switch contact materials
Gold (Au), recommended for low voltage actuator controlsOption:
Potentiometer or 0/4 20 mA (electronic position transmitter)Position feedback signal, analogue
(options)
Continuous indication, adjustable indicator disc with symbols OPEN and CLOSEDMechanical position indicator
Blinker transmitter (optional for modulating actuators)Running indication
Self-regulating PTC heater, 5 20 W, 110 250 V AC/DCStandard:Heater in switch compartment
24 48 V AC/DC (for actuators with 3-phase AC/1-phase AC/DC motors)
or 380 400 V AC (for actuators with 3-phase AC motors)
Options:
A resistance type heater of 5 W, 24 V AC is installed in the actuator in combination with AM or AC actu-
ator controls.
Service conditions
Indoor and outdoor use permissibleUse
Any positionMounting position
2 000 m above sea level
> 2,000 m above sea level, on request
Installation altitude
Refer to actuator name plateAmbient temperature
Up to 100 % relative humidity across the entire permissible temperature rangeHumidity
IP68 (with AUMA 3-phase/1-phase AC or DC motor)
For special motors differing enclosure protection available (refer to motor name plate)
Standard:Enclosure protection according to
EN 60529
DS Terminal compartment additionally sealed against interior (double sealed)Option:
According to AUMA definition, enclosure protection IP68 meets the following requirements:
Depth of water: Maximum 8 m head of water
Duration of continuous immersion in water: Maximum 96 hours
Up to 10 operations during flooding.
Modulating duty is not possible during continuous immersion.
For exact version, refer to actuator name plate.
Pollution degree 4 (when closed), pollution degree 2 (internal)Pollution degree according to IEC
60664-1
2 g, from 10 to 200 Hz (for actuators in AUMA NORM version)
1 g, from 10 to 200 Hz (for actuators with mounted AUMA actuator controls)
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Indications apply to actuators with AUMA 3-phase AC motor and AUMA plug/socket
connector.They are not valid in combination with gearboxes.
Vibration resistance according to
IEC 60068-2-6
68
SA 07.2 SA 16.2 /SAR 07.2 SAR 16.2
Technical data AM 01.1/AM 02.1