EasyManua.ls Logo

Automation Direct C-more EA1-T4CL - Page 115

Automation Direct C-more EA1-T4CL
181 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6–33
Chapter 6: PLC Communications
6
EA1-TCL-M Hardware User Manual, 2nd Ed., 10/10
®®®
User Constructed Cables – Wiring Diagrams (cont’d)
Diagram 18
Diagram 19
User Constructed
AutomationDirect CLICK PLC
Analog CPU
RS-485
CLICK
Com Port 3
Wiring Diagram
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
Use 120 ohm resistors as termination resistors (Term.)
3
5
RS-485
Signal A
Logic
Ground
9
11
5
1
RD+
SD+
shield
RS-485
Signal B
8 10
12
RD–
SD–
Term.
13
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = do not use
2 = do not use
1 = Frame GND
15 = do not use
14 = do not use
13 = Termination
12 = SD– (RS485)
11 = SD+ (RS485)
10 = RD– (RS485)
9 = RD+ (RS485)
1
15
15-pin
D-sub
(male)
To C-more Micro-Graphic
Serial Port2
+
-
LG
Term.
RS-485 Signal A
RS-485 Signal B
Logic Ground
AutomationDirect Productivity PAC
RS-485
Removable Connector
included with
Productivity3000 CPU
Wiring Diagram
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
Use 120 ohm resistors as termination resistors (Term.)
3
5
TXD+ / RXD+
Ground
9
11
5
1
RD+
SD+
shield
8 10
12
RD–
SD–
Term.
13
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = do not use
2 = do not use
1 = Frame GND
15 = do not use
14 = do not use
13 = Termination
12 = SD– (RS485)
11 = SD+ (RS485)
10 = RD– (RS485)
9 = RD+ (RS485)
1
15
15-pin
D-sub
(male)
To C-more Micro-Graphic
Serial Port2
+
-
G
Term.
TXD- / RXD-
TXD+ / RXD+
TXD- / RXD-
Ground
User Constructed

Table of Contents