6 Parameter Settings and Functions
48 © Copyright Reserved Autonics Co., Ltd.
6.1.6 SV High/Low-limit Settings
You can limit the SV (Setting Value) range within the temperature range of the sensor or
analog input type in order to prevent the system from controlling with improper SV.
Group Parameter Range
Factory
Default
Unit
Initial Setting Group
SV High-limit
See below.
1350
℃/℉
SV Low-limit -200
SV Low-limit : Low-limit sensor value to SV high-limit - 1 digit
SV High-limit : SV low-limit + 1 digit to high-limit sensor value
Attempts to set the limits outside the min/max input range, or
analog's high/low-limits, are not accepted. Instead, the previous
settings are retained.
SV (Setting Value) can only be set within the SV low-limit and
SV high-limit.
SV low-limit cannot exceed SV high-limit.
Changing the input sensors automatically changes the SV
high/low-limit settings to max/min values of the changed
specification (temperature sensor input), or to high/low-limit
scale values (analog input). The user is required to reset related
settings.