6 Parameter Settings and Functions 
© Copyright Reserved Autonics Co., Ltd.    89 
 
  When power is on, or in standard control or heating mode, the 
controller outputs 0% if HHHH is displayed and 100% if LLLL is 
displayed. 
  When power is on, or in standard control or cooling mode, the 
controller outputs 100% if HHHH is displayed and 0% if LLLL is 
displayed. 
  In heating and cooling mode, when power is on or in standard 
control, heating output is 0% and cooling output is 100% if 
HHHH is displayed; heating output 100% and cooling output is 
0% if LLLL is displayed. 
  Output priority in manual control: Heating(Cooling)_MV > 
Stop_MV > Sensor Error_MV 
  Output priority in automatic control: Stop_MV > Sensor 
Error_MV > Heating(Cooling)_MV 
6.6.5.1  Sensor Error MV. 
  This feature sets control output when a sensor open error occurs. Users can 
configure ON/OFF, MV settings, etc. 
  Ignores MV by ON/OFF control or PID control, and sends out a control value based 
on the defined MV. 
Group 
Preceding 
Condition 
Param
eter 
Range 
Factory 
Default 
Unit 
Control 
Setting 
Group 
Heating 
(Cooling) 
PID 
Sensor 
Error 
MV 
0.0 ~ 100.0 
0.0 
% 
ON/
OFF 
0.0 (OFF)/100.0 (ON) 
Heating 
and 
Cooling 
PID 
-100.0 (Cool) to 100.0 
(Heat) 
0.0 
ON/
OFF 
-100.0 (Cool ON)/0.0 
(OFF)/100.0 (Heat ON) 
6.6.6  Parameter Initialization 
This option resets all parameters in memory to factory defaults. 
Group  Parameter  Range 
Factory 
Default 
Unit 
Option Setting Group 
(Communication Setting) 
Parameter Initialize  YES/NO  NO  - 
 
 
  If selecting "Yes", all parameters will be initialized and temperature 
control will be by factory default. 
  However, communication parameters are not initialized.