6 Parameter Settings and Functions
82 © Copyright Reserved Autonics Co., Ltd.
6.5.3 Communications Parity Bit Settings
Parity bit is a data communication method that adds an additional bit to each character in
transmitted data as an indicator used to verify data loss and corruption. This parameter is
used to enable or disable the parity bit option.
SV (Setting Value) Description
NONE Disables parity bit.
EVEN Sets the total bits with signal value of 1 as even numbers.
ODD Sets the total bits with signal value of 1 as odd numbers.
Group Parameter Range
Factory
Default
Unit
Option Setting Group
(Communication Setting)
Parity Bit NONE, EVEN, ODD NONE -
6.5.4 Communication Stop Bit Settings
You can set the number of bits to mark the end of a transmitted data string.
Setting Value Description
1 Sets end of data string to 1 bit.
2 Sets end of data string to 2 bit.
Group Parameter Range
Factory
Default
Unit
Option Setting Group
(Communication Setting)
Stop Bit 1, 2 2 -
6.5.5 Response Wait Time Settings
Set a standby time to mitigate communication errors when communicating with a slow
master device (PC, PLC, etc.). Once a standby time is set, the controller will respond after
the defined standby time has elapsed.
Group Parameter Range
Factory
Default
Unit
Option Setting Group
(Communication Setting)
Response Wait
Time
5 ~ 99 20 ms
Shorter standby times can cause communication errors in the master
device.