6 Parameter Settings and Functions 
© Copyright Reserved Autonics Co., Ltd.    59 
 
※Reverting to power, the control starts with the MV of the power off. 
6.2.4.2  Manual control initial MV. 
If the baseline MV for manual control is configured to PR.MV (Preset Manual MV), you 
can set the initial MV for manual control. 
Group  Preceding Condition  Parameter  Range 
Factory 
Default 
Unit 
Control 
Setting 
Group 
Heating, Cooling, PID 
Preset MV 
0.0 ~ 100.0  0.0 
% 
Heating and Cooling, 
PID 
-100.0 (Cool) to 
0.0 to 100.0 
(Heat) 
0.0 
 
 
When in heating and cooling control, a setting between 0.1 and 100.0 
applies heating MV, and a setting between 0.1 and -100.0 applies 
cooling MV. 
6.2.5  Output Settings 
6.2.5.1  Control Output Settings 
If the control output type is a current or SSR output model, control output is supported at 
the same time, so the user can choose a suitable output type. 
Group  Parameter  Range 
Factory 
Default 
Unit 
Initial Setting Group  Output Type  Current, SSR  SSR  - 
 
 
The relevant parameter will be activated only if the model is TM2-□□C□ 
(current or SSR output type).