6 Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd. 81
If 00 is designated, communications are not performed.
6.5.2 Communications Speed Settings
You can set the rate of data transmission.
Group Parameter Range
Factory
Default
Unit
Option Setting Group
(Communication Setting)
Bits Per
Second
2400, 4800,
9600,19200,38400
9600 bps
A display LED corresponding to the current bps flashes for 5 seconds (1 second
intervals) when the power supply is initially ON.
LED TM2 Series TM4 Series
BPS (Bits Per
Second)
PWR PWR -
CH1 CH1 2400
CH2 CH2 4800
AL1 CH3 9600
AL2 CH4 19200
AL3 - 38400
AL4 - -
It is required to reset controller's POWER (Power OFF -> Power
ON) after changing communication speed (bps) via port B.
One module communication is allowed for Port A.
Communication speed is fixed to 9600 bps.
Make sure that each module has its own communication
address. If there are overlapping addresses, parameters for
overlapping module cannot be monitored and it may affect the
whole communication speed.
+0
+0
+16
+16

Table of Contents

Other manuals for Autonics TM4 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autonics TM4 Series and is the answer not in the manual?

Autonics TM4 Series Specifications

General IconGeneral
BrandAutonics
ModelTM4 Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals