C.1.3 Fault
Detector-/System faults registered on a BS-100 control panel will only give
message to that control panel and on the BU-units. On the BS-100 control
panel the fault message will appear in the display. Internal buzzer and
FAULT indication lamp will also be activated.
If the door is open on the BS-100 control panel, there will be no fault
message in the display. The message will appear when the door is closed.
On the BU-units the internal buzzer and the FAULT indication lamp will be
activated. (No text in the display)
Fault output (not comm.fault) on the EA- will be activated (output L59).
Only the BMA-output on the control panel which registered the fault will be
activated.
If a communication failure between the BS-100 control panel and the EA
occurs, the fault message will be printed out on the printer on the BU-units.
Comm.fault output BS-/EA- will be activated (output L61).
When there is a communication failure between the EA and the BU-units
the comm.fault output EA-/BU- will be activated (output L62).
C.1.4 More alarms
The "MORE ALARMS" indication lamp will light on the BS-100 control
panel which is registering more than one alarm. When there are two alarms
on different BS-100 control panels, the "MORE ALARMS" indication lamp
will not light.
The "MORE ALARMS" indication lamp on the BU-units will light if there
are more than one alarm registered in the system. Two alarm from two
different BS-100 control panels will activate the "MORE ALARMS"
indication lamp on the BU-units.
C.1.5 Device(s) still in alarm cond.
After "RESET" the "DEVICE(S) STILL IN ALARM COND." indication
lamp may light on the BS-100 control panels which still has addresses in
alarm condition. If this lamp lights on one of the BS-100 control panels, it
will also light on the BU-units.