6-18
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
Display Item Contents
Initial
value
User
level
Notes
MS indicating lamp
ON status
(1st priority)
0: Lit.
1: Slow flashing
2: Flashing twice
3: Fast flashing
4: Left to right
5: Right to left
6:
Reciprocating between left and right
7: Deviation OK
8: Deviation graph
9: MV graph
10: Heat-side MV graph (For heat/
cool control)
11: Cool-side MV graph (For heat/
cool control)
12: MFB graph (including MFB being
estimated)
13: DI monitor
14: Internal contact monitor
15: Internal event monitor
1 2
MS indicating lamp
ON condition
(2nd priority)
Same as Multi Status (MS) display,
Condition (top priority)
44 2
MS indicating lamp
ON status
(2nd priority)
Same as Multi Status (MS) display,
Status (top priority)
6 2
MS indicating lamp
ON condition
(3rd priority)
Same as Multi Status (MS) display,
Condition (top priority)
1 2
MS indicating lamp
ON status
(3rd priority)
Same as Multi Status (MS) display,
Status (top priority)
9 2
MS indicating lamp
deviation range
0 to 9999 U
5 2
Special function 0 to 15
(This value becomes “0” when the
power is turned ON.)
0 2
Zener barrier
adjustment
The value can be changed with the
adjustment.
The numeric value cannot be directly
input with the manual operation.
0.00 2
Displayed when the PV range
type is RTD and the special
function (C88) is set at “5”.
Number of CT1 turns 0: 800 turns
1 to 40: CT turns devided by 100.
8 2
If the controller model has 2
current transformer inputs,
this setting is displayed.
Number of CT1
power wire loops
0: 1 time
1 to 6: Number of times
1 2
Number of CT2 turns 0: 800 turns
1 to 40: CT turns devided by 100.
8 2
Number of CT2
power wire loops
0: 1 time
1 to 6: Number of times
1 2
PV input failure
(under range) type
0: –10 %FS
1: –5 mV (This setting is applicable if
C0
1
(PV input range type) is set for
sensor type B (No. 17) or PR40-20 (No.
23).)
0 0
If ROM version 1 in the
instrument information bank
(
i
d02
) is 2.26 or earlier,
this item cannot be selected.
Handling Precautions
If ROM version 1 of the instrument information bank(
I
d02
) is prior to
2.04, the setting options for [Number of CT1 turns], [Number of CT1
power wire loops], [Number of CT2 turns] and [Number of CT2 power
wire loops] are not displayed.