6-26
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
DO Assignment bank
Bank selection:
Display Item Contents
Initial
value
User
level
Notes
Control output 1
Operation type
0: Default output
1: MV 1 (ON/OFF control output,
time proportional output, and
time proportional output (heat) of
Heat/Cool control.)
2: MV2 (Time proportional output
(cool) of Heat/Cool control)
3: Function 1 ((A and B) or (C and D))
4: Function 2 ((A or B) and (C or D))
5: Function 3 (A or B or C or D)
6: Function 4 (A and B and C and D)
0 2
Displayed when control
output 1 of the model is
relay output or voltage pulse
output.
When using control output 1,
the default output is MV1.
Control output 1
Output assignment A
0: Normally opened. (OFF, 0)
1: Normally closed. (ON, 1)
2: Internal Event 1
3: Internal Event 2
4: Internal Event 3
5: Internal Event 4
6: Internal Event 5
7: Internal Event 6
8: Internal Event 7
9: Internal Event 8
10 to 13: Undefined.
14: MV1
15: MV2
16 to 17: Undefined.
18: DI1
19: DI2
20: DI3
21: DI4
22 to 25: Undefined.
26: Internal Contact 1
27: Internal Contact 2
28: Internal Contact 3
29: Internal Contact 4
30: Internal Contact 5
31 to 33: Undefined.
34: Communication DI1
35: Communication DI2
36: Communication DI3
37: Communication DI4
38: MANUAL mode
39: READY mode
40: RSP mode
41: AT running
42: During SP ramp
43: Undefined.
44: Alarm occurs.
45: PV alarm occurs.
46: Undefined.
47: mode key pressing status
48: Event output 1 status
49: Control output 1 status
14 2
Displayed when control
output 1 of the model is
relay output or voltage pulse
output, and the operation
type of control output 1 is set
1 to 4 (
Ot
1.
1
> 2).
Control output 1
Output assignment B
0 2
Control output 1
Output assignment C
0 2
Control output 1
Output assignment D
0 2
Control output 2
Polarity A to D
1st digit: Polarity A
2nd digit: Polarity B
3rd digit: Polarity C
4th digit: Polarity D
Digits are assigned from right to left
in the order 1, 2, 3, 4.
0: Direct
1: Reverse
0000 2
Control output 1
Polarity
0: Direct
1: Reverse
0 2
Control output 1
Latch
0: None
1: Latch (Latch at ON)
2: Latch (Latch at OFF except for
initialization at power ON)
0 2
(Continue on next page.)