EasyManua.ls Logo

Bender ISOMETER iso1685DP-425 - Address Setting and Termination; Setting the BMS Address

Bender ISOMETER iso1685DP-425
89 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Device communication
69
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
9.1.5 Address setting and termination
Correct address setting and termination is essential for proper functioning of the isoxx1685xx-
xxx series insulation monitoring device.
Ensure correct address setting and termination of the device!
9.1.6 Setting the BMS address
Set the BMS address ((1)2…90) in the device menu via the following path:
Device settings > Interface > BMS > BMS address.
CAUTION
Risk of bus errors!
Double assignment of addresses on the respective BMS busses can cause
serious malfunctions.
The ISOMETER® cannot switch on a potential termination at the BMS bus.
Even though this is not expected to cause communication problems, the
ISOMETER® should be operated as BMS slave if possible (BMS address > 1).
If no other device with master capabilities is available on the bus, the
ISOMETER® can be set to master (BMS address 1).
Before the ISOMETER® takes over the backup master function after being
switched on, it waits to see if another master connects to the system.
Waiting period: BMS address minus 1 = waiting period in minutes.
Example: The iso1685DP has BMS address 3. It waits 3 minus 1 minutes (= 2
minutes) for a master to connect.

Table of Contents

Related product manuals