EasyManua.ls Logo

Bender ISOMETER iso1685DP-425 - Settings in the Device Menu; Alarm Settings; Insulation Alarm

Bender ISOMETER iso1685DP-425
89 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Settings
44
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
8.2 Settings in the device menu
8.2 (1 ) Alarm settings
The limit values for the insulation resistances of alarm 1 and alarm 2 can be specified in the
alarm settings menu and the profile of the ISOMETER® can be adjusted. If the password query
has been enabled in the device menu (refer to "Password" on page 65), enter the device pass-
word in order to change the settings.
The following functions can be adjusted:
8.2 (1.1) Insulation alarm
In the Insulation alarm menu, the ISOMETER® limit values for alarm 1 and alarm 2 can be set.
Activation or deactivation of the two alarm levels R
an1
for alarm 1 and R
an2
for alarm 2 are il-
lustrated in the following graphic:
An alarm will become inactive as soon as the hysteresis of the set operating value is exceeded.
8.2 (1.1.1) Alarm 1
An insulation resistance of 200 …1 M can be set for alarm 1.
Condition: alarm 1 ≥ alarm 2.
8.2 (1.1.2) Alarm 2
An insulation resistance of 200 …1 M can be set for alarm 2.
8.2 (1.1.3) Fault memory
Automatic reset of inactive faults at the outputs
(relays 11-12-13, 21-22-24):
Response value ranges
The response value range depends on the device variant. For further infor-
mation on the response value ranges of individual variants, refer to chapter
12. "Technical data" from page 75.
•on If a fault becomes inactive, the programmed outputs remain in fault
condition until they are reset manually.
•off If a fault becomes inactive, the programmed outputs automatically
change their state.
t
R
R
an1
R
an2
Alarm 1
aktiv
Alarm 2
aktiv
Hysterese
Alarm 1
inaktiv
Hysterese
Alarm 2
inaktiv

Table of Contents

Related product manuals