It defines the action of the actuator in case of loss of the bus signal. The action takes
place only if the local selector is on REMOTE position and if the bus is operating.
When the bus signal restores, also the actuator restores at its normal functioning.
Value: 0: Off - disable (default setting)
1: Close
2: Open
3: Stayput
4: Go to position indicated in the parameter ‘Safe position’
Byte 5 Delay before initiating Fail Safe operation
It defines the delay before execute the programmed Safe Action
Value: minimum 0 sec.
maximum 255 sec.
default value: 4 sec.
Byte 6 Safe position
It defines the Safe position when ‘Safe Action: go to position’ is selected
Value: minimum 0 %
maximum 100%
default value: 50%
Byte 7 Timer Open Direction - status
It enables the Timer function in Open direction.
Value: 0: Off - disable (default setting)
1: On
Byte 8 Timer Open Direction On time
It defines the On time of the Timer function in opening
Value: minimum 2 sec.
maximum 200 sec.
default value: 2 sec.
Byte 9 Timer Open Direction Off time
It defines the Off time of the Timer function in opening
Value: minimum 1 sec.
maximum 200 sec.
default value: 2 sec.
Byte 10 Timer Open Direction Start position
It defines the start position of the Timer function in opening
Value: minimum 0%
maximum 100%
default value: 0%.
Byte 11 Timer Open Direction Stop position
It defines the stop position of the Timer function in opening
Value: minimum 100%
maximum 0%
default value: 100%.
Byte 12 Timer Close Direction - status
It enables the Timer function in Close direction.