© Copyright by BIFFI Italia. All right reserved. Section 618/42 Page 13
Contents may change without notice
Value: 0: Off - disable (default setting)
1: On
Byte 13 Timer Close Direction – On time
It defines the On time of the Timer function in closing
Value: minimum 2 sec.
maximum 200 sec.
default value: 2 sec.
Byte 14 Timer Close Direction – Off time
It defines the Off time of the Timer function in closing
Value: minimum 1 sec.
maximum 200 sec.
default value: 2 sec.
Byte 15 Timer Close Direction – Start position
It defines the start position of the Timer function in closing
Value: minimum 100%
maximum 0%
default value: 100%.
Byte 16 Timer Close Direction – Stop position
It defines the stop position of the Timer function in closing
Value: minimum 0%
maximum 100%
default value: 0%.
Byte 17 Reserved
Byte 18 Dead band
It defines in tenth of % the Dead band of the positioning function available on the
modulating actuator. The movement is inhibited until the difference between current
position and requested position (position error) is lower than Dead band.
Value: minimum 1 0,1%
maximum 255 22,5%
default value: 10 1,0%
Byte 19 Motion inhibit time
It defines the minimum delay between two cycles of the motor when the actuator is in
modulating service. It allows to adjust the number of start per hour of the electric motor.
Value: minimum 1 sec.
maximum 255 sec.
default value: 6 sec.