| | | * Extra dwell for handicapped accessible hall calls
| | | 1..30 [5] s
| | | * Parking
| | | off/10..65535 [off] s
| | | * If park floor changed, re-park after
| | | off/10..65535 [15] s
| | | * Allocation time low priority call
| | | 10..9999 [60] s
| | | * Allocation time high priority call
| | | 10..9999 [60] s
| | | * Allocation time direct run or lift allocation
| | | 10..9999 [60] s
| | | * Allocation time service position
| | | 1..30 [5] min
| | | * Car light off
| | | off/10..9999 [off] s
| | | * Display off
| | | off/3..9999 [off] s
| | | * Landing displays reduced
| | | off/3..9999 [off] s
| | | * Blue Modus C (Standby) on time
| | | off/1..65535 [30] min
| | | * Blue Modus C (Standby) off delay
| | | off/1..255 [4] s
| | | * Blue Modus B (Shut Down) on time
| | | off/30..65535 [off] min
| | | * Blue Modus B (Shut Down) off delay
| | | off/1..255 [30] s
| | | * Car fan run delay time
| | | off/1..255 [off] s
| | | * Max. car fan run time
| | | off/1..255 [off] min
| | | * Automatic air exchange interval (car fan)
| | | off/1..255 [off] min
| | | * Automatic air exchange duration (car fan)
| | | off/1..255 [off] min
| | | * Arrival indicator delay
| | | off/1..10 [off] s
| | | * Arrival indicator puls time
| | | Impulse/1..30 [3] s
| | | * Speech synthesis delay
| | | off/1..10 [off] s
| | | * Speech synthesis puls time
| | | 1..30 [3] s
| | | * Start inhibitor delay time
| | | off/1..15 [off] s
| | | * Selective blocking of hall call directions
| | | off/1..30 [off] s
| | | * Timespan for enabling calls disabled via menu
| | | off/1..120 [off] s
| | | * Signal duration disabled call selected
| | | off/1..60 [3] s
| | | * LCD-illumination
| | | always on/1..60 [15] min
| | | * Automatic LCD-menu homing
| | | off/10..255 [off] min
| | | * Blinking light pulse time (114)
| | | off/0.1..25.5 [off] s
| | | * Generic malfunction delayed (495)
| | | off/1..255 [10] s
| | | * Emergency call unit ready signal delay
| | | off/0.1..6500.0 [10.0] s
| | | * Clearing operation repeat time
| | | off/1..240 [off] min
| | | * Duration advance drive warning
| | | off/1..10 [off] s
| | | * System cold start delay
| | | off/1..255 [off] s
| | | * Automatic Test drive
| | | off/15..65535 [off] min
| | | * Time synchronization impulse
| | | - off [Default]
| | | - on
| | | * Time synchronization impulse, time of day
| | | 0..23 [0] o'clock
| | |
| | +- Monitoring times
| | | * Door close monitoring
| | | off/1..60 [20] s
| | | * Door open monitoring