1. Report the DX2010 fault to configured destination on address 140 when the fault is
detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
2. When the fault is reset, send the restored report to the configured destinations.
P The FAULT indicator is turned off, when there is no other system fault.
– Printer Failure
Module DX4010 Missing
Condition:
No communication with DX4010 if printer is available.
Restore:
4 Restore the communication with DX4010 to a normal condition and reset the fault.
Supervise:
1. Report the DX4010 missing fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
2. When the fault is reset, send the restored report to the configured destinations.
P The FAULT indicator is turned off, when there is no other system fault.
Printer Missing
Condition:
No communication with the printer available, if the printer is enabled and the DX4010 is in a
normal condition.
Restore:
4 Restore the communication with the printer to a normal condition and reset the fault.
Supervise:
1. Report the printer missing fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
2. When the fault is reset, send the restored report to the configured destinations.
P The FAULT indicator is turned off, when there is no other system fault.
Printer Fault
Condition:
The printer condition is abnormal (e.g. printer no paper/printer buffer is overflow/...) if printer
is enabled and the DX4010 is in a normal condition.
Restore:
4 Restore the printer to a normal condition and reset the fault.
Supervise:
1. Report the printer error to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
2. When the fault is reset, send the restored report to the configured destinations.
P The FAULT indicator is turned off, when there is no other system fault.
– RF Receiver Failure
RF Receiver 1 Fault
Condition:
The receiver condition is abnormal (e.g. RF micro is removed/hold RF micro in reset/...) if a
wireless module is enabled.
Restore:
4 Restore the communication with the receiver to a normal condition and reset the fault.
For more information, refer to RF Devices, page 78.
Supervise:
AMAX 2100 / 3000 / 4000
Troubleshooting | en 143