Receiver Transmission Format (Contact ID, SIA, Conettix IP)
Receiver 1 - 4 Transmission Format
The AMAX panel provides four kinds of transmission formats, Contact ID, SIA, SIA DC09 and
Conettix IP format for its dialing and communication features. You can select the transmission
format with address options to specify how to transmit the information to the base station
receiver. If Contact ID or SIA format is selected, the information is transmitted by telephone
line; if Conettix IP format is selected, then it is connected with B426 / DX4020 or ITS-
DX4020G GPRS. The default setting for the transmission format is Contact ID.
4 Program the transmission format for receiver 1, 2, 3, and 4 separately in address 023,
address 053, address 083, and address 113.
Contact ID Format
The Contact ID format can identify hundreds of zones by their unique codes. This format
provides a single-digit eent qualifier and a three-digit event code that quickly identifies the
reported condition.
In general, Contact ID format is very simple because most of the event codes and point ID
codes are predefined. The central monitoring station software usually can identify an alarmed
zone by its point ID code and usually pays little attention to the event code.
– Contact ID Message Format
– ACCT MT Q EEE GG CCC S
– ACCT = Subscriber ID
– MT = Message type, H
– Q = Event qualifier
– 1= New event or opening
– 3= New restore or closing
– 6= Previously reported off-normal event
– EEE = Event code
– GG = Group number (always 0)
– CCC = Zone/ contact ID, 000 is for no zone / ID message
– S = Checksum digit
Note: Any 0 values must be sent as an 0x0A.
Contact ID Report Data.
SIA Format
The AMAX panel supports the following SIA formats:
SIA DC 03
SIA DC 09
SIA allows transmitting system ID, event code, zone ID, area ID, event time, and also event
text.
Conettix IP Format
The AMAX panel supports Conettix IP format. An AMAX panel with DX4020G and B426 is able
to connect to Bosch Receivers 6600/6100 using the Conettix IP format.
Event Description
CID SIA ALL
Event
KP
Recall
Dialer
Event
EN
Event
SYSTEM RESET √ √
BURG ALARM 1130 BA √ √ √ √
BURG ALARM RESTORE 3130 BR √
BURG 24-HOUR 1133 BA √ √ √ √
34 en | Settings AMAX 2100 / 3000 / 4000