2-6
Bosch Security Systems 05/10 BLCC100I
Solution 16
plus
Installation Manual Installing the Hardware
KEYPAD EMERGENC Y A LA RM TRIG GER S
Key Sequence Event Triggered
Ë + Ê Hold for 2 seconds
Keypad Fire Alarm
Ê + È Hold for 2 seconds
Keypad Panic Alarm
È + Â Hold for 2 seconds
Keypad Medical Alarm
Table 5: Keypad Emergency Alarm Triggers
KEY PA D S E TU P
The Solution 16
plus
control panel can have a maximum of 8
keypads connected via the LAN terminals. Each keypad
must be set to a unique address before they will operate.
Each keypad needs to be assigned to a home area via MENU
6-1-3. This sets the area the keypad will display and control by
default. Keypads can be locked to a home area or allowed to
roam or move between areas.
When the system is powered up, any keypads which have not
been assigned a home area will be automatically set to home
area 1.
Set each keypad address using the table below as a guide.
i
Note
Only 1 Keypad can be assigned to each address. All Keypads are
supplied from the factory set to address 1. (OFF-OFF-OFF-OFF).
KEY PA D A D DR E SS SE LE C TI O N
4
Figure 10: Kyepad Address Selection
Keypad DIP Switch Address Settings
Keypad To Address S1 S2 S3 S4
Keypad 1 O O O O
Keypad 2 On O O O
Keypad 3 O On O O
Keypad 4 On On O O
Keypad 5 O O On O
Keypad 6 On O On O
Keypad 7 O On On O
Keypad 8 On On On O
Table 6: Keypad DIP Switch Address Settings
STATU S I C O NS & L ED IN DICATOR S
The following table lists the function of each of the ICON
Symbols and LED Indicators on the Graphic Keypad Display.
Icon Status Meaning
The keypad can display the current status of up to
4 areas simultaneously via the Area Icon Indicators.
This option can be disabled in MENU 6-1-4
On The area is turned All On or Part On
O The area is turned O
Flashing
Fast
The area has an alarm
On System power is normal
Flashing System power is missing
Flashing A re alarm is active
O No re alarm
On
Fire alarm in memory (Turn the area
All On and O to Clear).
On
The existing service or trouble
condition has been acknowledged.
O No service or trouble conditions exist
Flashing
A service / trouble condition is present
that has not been acknowledged.
On The area is turned Part On.
O
The area is not turned Part On.
On The area is turned o.
O The area is turned All On or Part On
On The area is turned All On
O The area is turned O
On You have mail waiting to be read
O No Mail
On
Area is ready to turn on
(All On / Part On)
O Not ready, Zone Open


On All On
Flashing
Alarm


On Area is o.
Flashing Area not ready to turn on



Flashing Installer programming mode is active.
Table 7: ICON & LED Indicator Meanings