8-4
Bosch Security Systems 05/10 BLCC100I
Solution 16
plus
Installation Manual Output Programming
28 – End Of Exit Time
This event type will cause the output to operate when the Exit Time
expires and will reset when the corresponding area is disarmed.
29 – Chime On
This event type will cause the output to operate when Chime Mode is
activated and will reset when Chime Mode is turned o.
If the event assignment for this output is set to zero (all areas), then
the output will operate as soon as Chime Mode is activated in any
area and will reset when Chime Mode is turned o in all areas.
30 - Chime Zone Faulted
This event type will cause the output to operate when a specic
Chime Zone is triggered and reset when the Chime Zone reseals.
If the event assignment for this output is set to zero (all areas), then
the output will operate as soon as any chime zone is triggered
provided that Chime Mode is on in those areas. The output will reset
when all Chime Zones are resealed. For this event type to work Chime
Mode must be turned on. See MENU 2-0-5 — Chime On/O
31 – Auto Arm Pre-Alert
This event type will cause the output to operate when the Auto
Arm Pre-Alert Timer is active and will reset when the Pre-Alert Timer
expires or a valid user code is entered.
New - Software Version 1.02 and later allows the output to reset
when the auto arm pre-alert time has been delayed by by the
user .
32 – Ready To Arm All On
This event type will cause the output to operate when the area is
disarmed and all zones in the area are sealled. The output will reset
when the area is armed or when a zone becomes unsealed.
If the event assignment for this output is set to zero (all areas), then
the output will only operate if all areas are disarmed and all zones
are sealed. The output will reset if any area is armed or if any zone
becomes unsealed.
33 – Ready To Arm Part On
This event type will cause the output to operate when the area is
disarmed and all zones in the area which are to be monitored in Part
On mode are sealed. The output will reset when the area is armed or
when a Part On zone becomes unsealled.
If the event assignment for this output is set to zero (all areas), then
the output will only operate if all areas are disarmed and all Part On
zones are sealed. The output will reset if any area is armed or if any
Part On zone becomes unsealed.
34 – Ready To Arm Part 2 On
This event type will cause the output to operate when the area is
disarmed and all zones in the area which are to be monitored in Part 2
On mode are sealled. The output will reset when the area is armed or
when a Part 2 On zone becomes unsealed.
If the event assignment for this output is set to zero (all areas), then
the output will only operate if all areas are disarmed and all Part 2 On
zones are sealed. The output will reset if any area is armed or if any
Part 2 On zone becomes unsealed.
35 – ‘Close’ Report Sent OK
This event type will cause the output to operate when the Closing
report has been acknowledged (Kissed-O ) by the control room
receiver. The output will reset when the area is disarmed. If the
output has been assigned to multiple areas then it will only reset
when all areas have been disarmed.
36 – External Siren (Spk Beeps)
This event type will cause the output to operate when any audible
alarm occurs. The output will reset when the system or area is
disarmed.
This event type will also generate speaker beeps when the system or
area is armed via a RF Keyfob, the Programmable Input Terminal or
Keyswitch zone.
1 beep when the area is disarmed
2 beeps when the area is armed All On
3 beeps when the area is armed Part On
37 – Internal Siren
This event type will cause the output to operate when any audible
alarm occurs. The output will reset when the system or area is
disarmed. No speaker beeps are generated for this event type.
38 – Alarm Any (Silent or Audible)
This event type will cause the output to operate when any silent or
audible alarm occurs. The output will reset when the system or area is
disarmed
39 – Fire Alarm
This event type will cause the output to operate when any audible re
zone or keypad emergency re alarm occurs. The output will reset
when the system or area is disarmed.
40 – Burglary Alarm
This event type will cause the output to operate when any audible
burglary alarm (including keypad emergency panic, medical and
tamper alarm) occurs. The output will reset when the system or area
is disarmed.
41 – Silent Alarm
This event type will cause the output to operate when any silent alarm
occurs (including silent re and silent keypad emergency alarms). The
output will reset when the system or area is disarmed.
New - Software Version 1.07 and later now correctly follows the
silent alarm zone setting for 24hr hold up zone types. Previous
software versions would not operate an output programmed for
silent alarm when a 24hr hold up zone was in alarm.
42 – Duress Alarm
This event type will cause the output to operate when a user initiates
a Duress alarm.
43 – Keypad Medical
This event type will cause the output to operate when a silent or
audible medical alarm has been initiated from the keypad. The
output will reset when the system or area is disarmed.
To initiate a medical emergency via the keypad, simultaneously press
and hold the [7] and [9] keys for 2 seconds.
44 – Keypad Fire
This event type will cause the output to operate when a silent or
audible re alarm has been initiated from the keypad. The output will
reset when the system or area is disarmed.
To initiate a re emergency via the keypad, simultaneously press and
and hold the [4] and [6] keys for 2 seconds.
45 – Keypad Panic
This event type will cause the output to operate when a silent or
audible panic alarm has been initiated from the keypad. The output
will reset when the system or area is disarmed.